outletControlOffCmd OBJECT-TYPE
SYNTAX Integer32 (-1..99999)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Outlet control command.
Once the command is issued, the outlet will turn Off immediately.
0-n : Time in seconds until the outlet command is issued
-1 : Cancel a pending outlet Off command
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
commands. These will respond with an error if a command value of > 0 is written to this object."


 
 