Description:
|
upsAddlFuncsStatusFault OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"This object contains 8 bits of information about the current
fault conditions of the UPS. The bits are encoded as
follows:
BIT 7: reserved for future use
BIT 6: reserved for future use
BIT 5: reserved for future use
BIT 4: 1=UPS fault - DC imbalance, UPS in bypass
BIT 3: 1=UPS fault - output voltage select failure, UPS
in bypass
BIT 2: 1=UPS fault - bypass supply failure
BIT 1: 1=UPS fault - Isolation Unit fan failure
BIT 0: 1=UPS fault - Electronics Unit fan failure, UPS
in bypass
Note that bit 0 is the low-order bit."
|
|
|
|