Main page
OID Repository
https://oid-base.com
Display OID:

{iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) 52 mibs(4) ctron(1) ctSystem(5) ctUPowerSupply(4) ctUPS(1) upsStatus(6) upsStatusTable(1) upsStatusEntry(1) upsStatusFault(2)}

upsStatusFault(2)

 
 

OID description



 
OID: (ASN.1 notation)
(dot notation)
(OID-IRI notation)

Description:

upsStatusFault OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"This object contains 8 bits of information about the current
fault conditions of the UPS. The bits are encoded as
follows:
BIT 7: 1=UPS fault - internal temperature has exceeded
nominal limits
BIT 6: 1=UPS fault - bypass relay (where applicable) malfunction
BIT 5: 1=UPS fault - battery charger failure
BIT 4: 1=UPS in shut down mode via `S' command
BIT 3: 1=UPS in `sleep' mode via `@ddd' command
BIT 2: 1=UPS fault - main relay malfunction
BIT 1: 1=UPS unable to transfer to on-battery operation
due to overload
BIT 0: 1=UPS's output unpowered due to low battery shut down
Note that bit 0 is the low-order bit."



Classification:

MIB object for network management

 
See classes of OIDs
 
 
Short link:


Parent OID: upsStatusEntry(1) Next sibling OID: upsStatusTemp(3) Last sibling OID: upsStatusTemp(3)