{iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) 52 mibs(4) ctron(1) ctPhysical(1) ctUPS(10) upsAddlFuncs(9) upsAddlFuncsTable(1) upsAddlFuncsEntry(1) upsAddlFuncsStatusFault(6)}

upsAddlFuncsStatusFault(6)

 
 

OID description



 
OID: (ASN.1 notation)
(dot notation)
(OID-IRI notation)

Description:

upsAddlFuncsStatusFault OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"This object contains 8 bits of information about the current
fault conditions of the UPS. The bits are encoded as
follows:
BIT 7: reserved for future use
BIT 6: reserved for future use
BIT 5: reserved for future use
BIT 4: 1=UPS fault - DC imbalance, UPS in bypass
BIT 3: 1=UPS fault - output voltage select failure, UPS
in bypass
BIT 2: 1=UPS fault - bypass supply failure
BIT 1: 1=UPS fault - Isolation Unit fan failure
BIT 0: 1=UPS fault - Electronics Unit fan failure, UPS
in bypass
Note that bit 0 is the low-order bit."



Classification:

MIB object for network management

 
See classes of OIDs
 
 
Short link:


Parent OID: upsAddlFuncsEntry(1) First sibling OID: upsAddlFuncsNumBatteryPacks(1) Previous sibling OID: upsAddlFuncsStatusOperational(5) Next sibling OID: upsAddlFuncsConfigPassword(7) Last sibling OID: upsAddlFuncsConfigBypass(9)