Description:
|
upsStatusOperational OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"This object contains 8 bits of information about the current
operational status of the UPS. The bits are encoded as
follows:
BIT 7: 1=replace battery condition
BIT 6: 1=low battery condition
BIT 5: 1=overloaded output condition
BIT 4: 1=on-battery mode of operation
BIT 3: 1=on-line mode of operation
BIT 2: 1=Smart Boost mode of operation (where applicable)
BIT 1: 1=UPS shut down due to low battery, overload,
or `sleep' mode
BIT 0: 1=run time calibration running
Note that bit 0 is the low-order bit."
|
|
|
|