Description:
|
trapCritical NOTIFICATION-TYPE
OBJECTS {trapCode, trapDescription, trapDeviceDescr, trapDeviceMgmtIP}
STATUS current
DESCRIPTION
"A critical alarm has occurred. Action: Check the Trap Details for more information."
-- #TYPE "Critical Alarm"
-- #SEVERITY CRITICAL
-- #CATEGORY "PowerDevice"
-- #SIMPLE_SEVERITY CRITICAL
-- #HWSTATUS_CATEGORY POWER
-- #SUMMARY " %s from %s %s"
-- #ARGUMENTS {2, 3, 0}
-- PDU Critical Alarm trap text: Description:
-- Voltage High Critical The PDU has detected an input line voltage that is more than 20% ABOVE the expected voltage
-- Voltage Low Critical The PDU has detected a very low input line voltage more than 20% BELOW the expected voltage, or the breaker may have tripped.
-- Load Critical The rated capacity of the breaker has been exceeded. There is a high risk of tripping the breaker
-- Current Critical Current has exceeded the breaker rating level. The addition of any new load could overload or trip the breaker
-- Total Power Critical The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection
-- Total Heat Critical The heat created by the load attached to this PDU has exceeded the set threshold
-- Total Load Critical The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection
-- iPDU Critical Alarm trap text: Description:
-- Voltage High The voltage for the iPDU is above the warning or critical limit
-- Voltage Low The voltage for the iPDU is below the warning or critical limit
-- Total PDU Load The total load of the iPDU is above the warning or critical limit
-- Phase Load The phase load is above the warning or critical limit
-- Load Segment Current The current for the circuit breaker is above the warning or critical limit
-- Managed Ext. Bar Communication An Intelligent Extension Bar can no longer communicate with the iPDU
-- Display Communication The Display Module can no longer communicate with the iPDU
-- Redundant Communication The iPDU cannot communicate with the redundant PDU or there is a redundancy configuration error
-- Remote PDU IP Mismatch The redundant PDU is already configured for redundancy with another PDU
-- Remote Outlet Control Disabled The redundant PDU outlet control settings are disabled and will therefore not allow redundant management control of its outlets
-- PDU Communication The Primary iPDU cannot communicate with the Secondary ipdu
|
|
|
|
|
|