riThHysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The hysteresis value for the threshold. After a
variable's threshold is triggered, the value of the variable must
either drop below or rise above a certain value (depending on the
setting of the Direction of Approach to Thresh variable), the
hysteresis, before another trigger can be recognized. For example,
if you set the threshold for module temperature to 80, the threshold
is triggered the first time the temperature rises above 80. If you
also set the hysteresis for this threshold to 60, the threshold will
only be triggered again if the temperature drops below 60, and then
rises past 80. If the temperature drops from 80 to 70, and then goes
back to 80, the threshold is not triggered. If the hysteresis value is
less than the threshold value, the variable's value must drop below the
hysteresis before another trigger is recognized. If the hysteresis value
is greater than the threshold value, the variable's value must rise above
the hysteresis before another trigger is recognized. The value of the
hysteresis depends on the value of the threshold and whether the value of
the variable is rising or falling; therefore, set this variable in conjunction
with both the Threshold Value and Direction of Approach to Thresh variables.
This variable is relevant only to thresholds set on Gauge variables."
|
|