Main page
OID Repository
https://oid-base.com
Display OID:

{iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) 2606 cmcTc(4) cmcTcStatus(2) cmcTcStatusSensorUnit2(4) cmcTcStatusUnit2Msg(7) cmcTcUnit2MsgTable(2) cmcTcUnit2MsgEntry(1) unit2MsgStatus(3)}

unit2MsgStatus(3)

 
 

OID description



 
OID: (ASN.1 notation)
(dot notation)
(OID-IRI notation)

Description:

unit2MsgStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvail(1),
configChanged(2),
error(3),
ok(4),
alarm(5),
warning(6),
tooLow(7),
tooHigh(8),
setOff(9),
setOn(10),
open(11),
closed(12),
locked(13),
unlRemote(14),
unlReaderKeypad(15),
unlSNMP(16),
unlWEB(17),
unlTimer(18),
noAccess(19),
circuit1 (20),
circuit2 (21),
lowBatt (22)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Actual message status
1: not available
2: configuration has changed (sensor new, changed, lost)
3: error
4: OK
5: alarm, e.g. smoke, vibration...
6: warning of analog value, value reached warning threshold
7: analog value too low, value reached low threshold
8: analog value too high, value reached high threshold
9: output is set to OFF
10: output is set to ON
11: door is open
12: door is closed
13: door is locked
14: door is unlocked by remote input, e.g. external cardreader
15: door is unlocked by reader or keypad connected to I2C
16: door is unlocked by SNMP set command (unit1OutputSet)
17: door is unlocked by WEB
18: door is unlocked by timer
19: no access, wrong keycode or cardnumber
20: orientation of PSM-Unit is circuit 1
21: orientation of PSM-Unit is circuit 2
22: battery low, wireless sensor"