Description:
|
pduOutletSwitchControl OBJECT-TYPE
SYNTAX INTEGER {cancel(1), on(2), onAfterDelay(3), off(4), offAfterDelay(5), reboot(6), rebootAfterDelay(7), none(8)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Used for manual control of the outlet. If the outlet is in manual
mode, this field can be set to one of the following values:
1 = Cancel pending operation
2 = Turn outlet on
3 = After delay (pduOutletSwitchOnDelay), turn outlet on
4 = Turn outlet off
5 = After delay (pduOutletSwitchOffDelay), turn outlet off
6 = Reboot: turn off, delay (pduOutletSwitchRebootHoldDelay), turn
outlet back on
7 = After delay (pduOutletSwitchRebootDelay), reboot outlet
When not in manual mode, setting this field will give an
inconsistentValue error. Returns none(8) for all get requests."
|
|
|
|
|
|