Description:
|
tempHumidSensorTempEvent NOTIFICATION-TYPE
OBJECTS {systemLocation, tempHumidSensorID, tempHumidSensorName, tempHumidSensorTempStatus, tempHumidSensorTempValue, tempHumidSensorTempLowThresh, tempHumidSensorTempHighThresh, tempHumidSensorTempScale, eventStatusText, eventStatusCondition}
STATUS current
DESCRIPTION
"Temperature/humidity sensor temperature event. If enabled,
this trap is sent when the tempHumidSensorTempStatus
indicates an error state ('tempLow' or 'tempHigh').
This trap is repeated periodically while the
tempHumidSensorTempStatus remains in an error state. If
the tempHumidSensorTempStatus returns to a non-error state
('normal'), this trap is sent once more with the non-error
tempHumidSensorTempStatus, and then stops being repeated."
-- #TYPE "Sentry: T/H Sensor Temperature Event."
-- #SUMMARY "Temperature Status of T/H Sensor '%s' (%s) is '%s'."
-- #ARGUMENTS {2, 1, 8}
-- #SEVERITY CRITICAL
-- #GENERIC 6
-- #CATEGORY "Error Events"
-- #SOURCE_ID "A"
-- #TIMEINDEX 255
-- #HELP ""
-- #HELPTAG 0
-- #STATE UNKNOWN
|
|
|
|
|
|