tempHumidSensorStatusEvent NOTIFICATION-TYPE
OBJECTS {systemLocation, tempHumidSensorID, tempHumidSensorName, tempHumidSensorStatus, eventStatusText, eventStatusCondition}
STATUS current
DESCRIPTION
"Temperature/humidity sensor status event. If enabled, this
trap is sent when the tempHumidSensorStatus indicates an
error state ('lost'). This trap is repeated periodically
while the tempHumidSensorStatus remains in an error state.
If the tempHumidSensorStatus returns to a non-error state
('found'), this trap is sent once more with the non-error
tempHumidSensorStatus, and then stops being repeated.
While the tempHumidSensorStatus indicates an error state, all
temperature and humidity status traps are suppressed for the
temperature/humidity sensor."
-- #TYPE "Sentry: T/H Sensor Status Event."
-- #SUMMARY "Status of T/H Sensor '%s' (%s) is '%s'."
-- #ARGUMENTS {2, 1, 4}
-- #SEVERITY CRITICAL
-- #GENERIC 6
-- #CATEGORY "Error Events"
-- #SOURCE_ID "A"
-- #TIMEINDEX 255
-- #HELP ""
-- #HELPTAG 0
-- #STATE UNKNOWN
|
|
|
|
|
|