{iso(1) identified-organization(3) dod(6) internet(1) mgmt(2) mib-2(1) upsMIB(33) upsConformance(3) upsCompliances(1) upsFullCompliance(3)}

upsFullCompliance(3)

 
 

OID description



 
OID: (ASN.1 notation)
(dot notation)
(OID-IRI notation)

Description:

upsFullCompliance MODULE-COMPLIANCE
STATUS current
DESCRIPTION
"The compliance statement for UPSs that support advanced full-featured functions."
MODULE -- this module
MANDATORY-GROUPS {upsFullIdentGroup, upsFullBatteryGroup, upsFullInputGroup, upsFullOutputGroup, upsFullAlarmGroup, upsFullTestGroup, upsFullControlGroup, upsFullConfigGroup}
OBJECT upsAlarmDescr
DESCRIPTION
"Support of all `well known' alarm types is not required. The well known alarm types which must be supported are: upsAlarmBatteryBad, upsAlarmOnBattery, upsAlarmLowBattery, upsAlarmDepletedBattery, upsAlarmTempBad, upsAlarmInputBad, upsAlarmOnBypass, upsAlarmBypassBad, upsAlarmOutputOffAsRequested, upsAlarmUpsOffAsRequested, upsAlarmUpsOutputOff, upsAlarmUpsSystemOff, upsAlarmGeneralFault, upsAlarmDiagnosticTestFailed, upsAlarmCommunicationsLost, upsAlarmShutdownPending, and upsAlarmTestInProgress."
OBJECT upsTestId
DESCRIPTION
"Support of all `well known' test types is not required. The well known test types which must be supported are: upsTestNoTestsInitiated, upsTestGeneralSystemsTest, and upsTestQuickBatteryTest."
OBJECT upsOutputSource
SYNTAX INTEGER {normal(3), battery(5)}
DESCRIPTION
"Support of the values other(1), none(2), bypass(4), booster(6) and reducer(7) is not required."
GROUP upsFullBypassGroup
DESCRIPTION
"The upsFullBypassGroup is only required for UPSs that have a Bypass present."
OBJECT upsShutdownType
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required, i.e., compliant systems need not support more than one shutdown type."
OBJECT upsAutoRestart
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required, i.e., compliant systems need not support more than one restart type."
OBJECT upsConfigInputVoltage
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
OBJECT upsConfigInputFreq
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
OBJECT upsConfigOutputVoltage
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
OBJECT upsConfigOutputFreq
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
OBJECT upsConfigLowBattTime
DESCRIPTION
"Implementation of all possible values may be onerous for some systems. Consequently, not all possible values must be supported. However, at least two different manufacturer-selected values must be supported."



Classification:

MIB object for network management

 
See classes of OIDs

Information:

Automatically extracted from IETF RFC 1628 with Errata 4831 applied.


Note to implementers:




 
 
Short link:


Parent OID: upsCompliances(1) First sibling OID: upsSubsetCompliance(1) Previous sibling OID: upsBasicCompliance(2)