Description:
|
upsSubsetCompliance MODULE-COMPLIANCE
STATUS current
DESCRIPTION
"The compliance statement for UPSs that only support the two-contact communication protocol."
MODULE -- this module
MANDATORY-GROUPS {upsSubsetIdentGroup, upsSubsetBatteryGroup, upsSubsetInputGroup, upsSubsetOutputGroup, upsSubsetAlarmGroup, upsSubsetControlGroup, upsSubsetConfigGroup}
OBJECT upsBatteryStatus
SYNTAX INTEGER {batteryNormal(2), batteryLow(3)}
DESCRIPTION
"Support of the values unknown(1) and batteryDepleted(4) is not required."
OBJECT upsAlarmDescr
DESCRIPTION
"Support of all `well known' alarm types is not required. The well known alarm types which must be supported are: upsAlarmOnBattery, upsAlarmLowBattery, upsAlarmInputBad, upsAlarmUpsOutputOff, upsAlarmUpsSystemOff, and upsAlarmTestInProgress."
OBJECT upsOutputSource
SYNTAX INTEGER {normal(3), battery(5)}
DESCRIPTION
"Support of the values other(1), none(2), bypass(4), booster(6) and reducer(7) is not required."
OBJECT upsShutdownType
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required, i.e., compliant systems need not support more than one shutdown type."
OBJECT upsAutoRestart
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required, i.e., compliant systems need not support more than one restart type."
OBJECT upsConfigInputVoltage
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
OBJECT upsConfigInputFreq
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
OBJECT upsConfigOutputVoltage
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
OBJECT upsConfigOutputFreq
MIN-ACCESS read-only
DESCRIPTION
"Read-write access is not required."
|
|
|
|
|
|
|
|