{iso(1) identified-organization(3) dod(6) internet(1) mgmt(2) mib-2(1) upsMIB(33) upsObjects(1) upsControl(8) upsShutdownAfterDelay(2)}

upsShutdownAfterDelay(2)

 
 

OID description



 
OID: (ASN.1 notation)
(dot notation)
(OID-IRI notation)

Description:

upsShutdownAfterDelay OBJECT-TYPE
SYNTAX INTEGER (-1..2147483647)
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then
nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect,
the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect."



Classification:

MIB object for network management

 
See classes of OIDs

Information:

Automatically extracted from IETF RFC 1628 with Errata 3276 applied.


Note to implementers:




 
 
Short link:


Parent OID: upsControl(8) First sibling OID: upsShutdownType(1) Previous sibling OID: upsShutdownType(1) Next sibling OID: upsStartupAfterDelay(3) Last sibling OID: upsAutoRestart(5)