Description:
|
eoEnergyParametersIntervalNumber OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-create
STATUS current
DESCRIPTION
"The number of intervals maintained in the eoEnergyTable.
Each interval is characterized by a specific
eoEnergyCollectionStartTime, used as an index to the
table eoEnergyTable. Whenever the maximum number of
entries is reached, the measurement over the new interval
replaces the oldest measurement. There is one exception
to this rule: when the eoEnergyMaxConsumed and/or
eoEnergyMaxProduced are in (one of) the two oldest
measurement(s), they are left untouched and the next
oldest measurement is replaced."
DEFVAL { 10 }
|
|
|
|