Description:
|
eoPowerAccuracy OBJECT-TYPE
SYNTAX Integer32 (0..10000)
UNITS "hundredths of percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This object indicates a percentage value, in hundredths of a
percent, representing the assumed accuracy of the usage
reported by eoPower. For example, the value 1010 means
the reported usage is accurate to +/- 10.1 percent. This
value is zero if the accuracy is unknown or not
applicable based upon the measurement method.
ANSI and IEC define the following accuracy classes for
power measurement:
IEC 62053-22 60044-1 class 0.1, 0.2, 0.5, 1 3.
ANSI C12.20 class 0.2, 0.5"
|
|
|
|