oid: "1.3.6.1.4.1.850.1.3.2.1.4"
short-description: "tlpAlarmTableRef OBJECT-TYPE"
last-modified: "2025-04-30"
parent-oid: "1.3.6.1.4.1.850.1.3.2.1"
---

## OID: `1.3.6.1.4.1.850.1.3.2.1.4`

```asn1
{iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) 850 tlpProducts(1) tlpAlarms(3) tlpAlarmTable(2) tlpAlarmEntry(1) tlpAlarmTableRef(4)}
```

### Description

```asn1
tlpAlarmTableRef OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This value references the OID of a table object applicable to the alarm
condition. This, in conjunction with the table row as defined by
tlpAlarmTableRowRef, specifies the object/row within this table to which
the alarm condition applies.
Example 1 -- The following sample values will be returned for a ups on
battery:
tlpAlarmId 28
tlpAlarmDescr tlpUpsAlarmOnBattery
tlpAlarmTime 12345678
tlpAlarmTableRef tlpDeviceTable
tlpAlarmTableRowRef tlpDeviceIndex.2
tlpAlarmDetail On Battery
tlpAlarmType warning
tlpAlarmState active
tlpAlarmAcknowledged notAcknowledged
tlpAlarmSeverity warning
In the above example, tlpAlarmTableRef references the device table and
tlpAlarmTableRowRef references the 2nd managed device in that table.
Example 2 -- The following sample values will be returned for a pdu with
a load turned off:
tlpAlarmId 46
tlpAlarmDescr tlpPduAlarmLoadOff
tlpAlarmTime 12345678
tlpAlarmTableRef tlpPduOutletTable
tlpAlarmTableRowRef tlpOutletIndex.1.4
tlpAlarmDetail Load Off
tlpAlarmType warning
tlpAlarmState active
tlpAlarmAcknowledged acknowledged
tlpAlarmSeverity warning
In the above example, tlpAlarmTableRef references the pdu outlet table and
tlpAlarmTableRowRef references the 4th outlet on the 1st managed device."
```

**Classification:** MIB object for network management

### Child OIDs

No child OID

### Terms of Use

[Terms of use](https://oid-base.com/disclaimer.htm.md)

**Note to implementers:**: The OID repository is constantly updated but does not necessarily store the latest (or most accurate) version of this formal description. For an implementation, it is recommended to search the web for a more recent description. If this is the case, please update the above description.