oid: "1.3.6.1.4.1.850.1.1.9.4"
short-description: "upsRebootDuration OBJECT-TYPE"
last-modified: "2019-01-04"
parent-oid: "1.3.6.1.4.1.850.1.1.9"
---

## OID: `1.3.6.1.4.1.850.1.1.9.4`

```asn1
{iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) 850 tlpProducts(1) tlpHardware(1) upsControl(9) upsRebootDuration(4)}
```

### Description

```asn1
upsRebootDuration OBJECT-TYPE
SYNTAX INTEGER (-1..100)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this object will immediately shutdown (i.e.,
turn off) either the UPS output or the UPS system (as
determined by the value of the upsShutdownType at the time
of shutdown) for a period equal to the indicated
number of seconds, after which time the output will be
started, including starting the UPS, if necessary. If
the number of seconds required to perform the request
is greater than the requested duration, then the
requested shutdown and startup cycle shall be
performed in the minimum time possible, but in no case
shall this require more than the requested duration
plus 60 seconds. When read, upsRebootDuration shall
return the number of seconds remaining in the
countdown, or -1 if no countdown is in progress. If
the startup should occur during a utility failure, the
startup shall depend on the value of upsAutoRestart
at that time.
UNITS seconds"
```

**Classification:** MIB object for network management

### Child OIDs

No child OID

### Terms of Use

[Terms of use](https://oid-base.com/disclaimer.htm.md)

**Note to implementers:**: The OID repository is constantly updated but does not necessarily store the latest (or most accurate) version of this formal description. For an implementation, it is recommended to search the web for a more recent description. If this is the case, please update the above description.