oid: "1.3.6.1.4.1.850.1.1.3.4.5.5.1.1"
short-description: "tlpAtsConfigHighVoltageTransfer OBJECT-TYPE"
last-modified: "2021-09-15"
parent-oid: "1.3.6.1.4.1.850.1.1.3.4.5.5.1"
---

## OID: `1.3.6.1.4.1.850.1.1.3.4.5.5.1.1`

```asn1
{iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) 850 tlpProducts(1) tlpHardware(1) tlpDeviceTypes(3) tlpAts(4) tlpAtsConfig(5) tlpAtsConfigVoltageRangeTable(5) tlpAtsConfigVoltageRangeEntry(1) tlpAtsConfigHighVoltageTransfer(1)}
```

### Description

```asn1
tlpAtsConfigHighVoltageTransfer OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The maximum line voltage allowed on the input source before the unit
disconnects the AC input connection. tlpAtsConfigHighVoltageTransfer is the
same value for both input sources on some units. On such units, changing
this value on one source will change the value on the other source. The
maximum value allowed is dictated by tlpAtsInputHighTransferVoltageUpperBound
(inclusively). The minimum value allowed is dictated by tlpAtsConfigHighVoltageReset.
This value may not be configurable on all models. If not supported, this value will
return ERROR_NO_SUCH_NAME."
```

**Classification:** MIB object for network management

### Child OIDs

No child OID

### Terms of Use

[Terms of use](https://oid-base.com/disclaimer.htm.md)

**Note to implementers:**: The OID repository is constantly updated but does not necessarily store the latest (or most accurate) version of this formal description. For an implementation, it is recommended to search the web for a more recent description. If this is the case, please update the above description.