oid: "1.3.6.1.4.1.534.6.6.7.6.6.1.3"
short-description: "outletControlOffCmd OBJECT-TYPE"
last-modified: "2022-01-26"
parent-oid: "1.3.6.1.4.1.534.6.6.7.6.6.1"
---

## OID: `1.3.6.1.4.1.534.6.6.7.6.6.1.3`

```asn1
{iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) 534 products(6) pduAgent(6) eatonEpdu(7) outlets(6) outletControlTable(6) outletControlEntry(1) outletControlOffCmd(3)}
```

### Description

```asn1
outletControlOffCmd OBJECT-TYPE
SYNTAX Integer32 (-1..99999)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Outlet control command.
Once the command is issued, the outlet will turn Off immediately.
0-n : Time in seconds until the outlet command is issued
\-1 : Cancel a pending outlet Off command
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
commands. These will respond with an error if a command value of > 0 is written to this object."
```

**Classification:** MIB object for network management

### Child OIDs

No child OID

### Terms of Use

[Terms of use](https://oid-base.com/disclaimer.htm.md)

**Note to implementers:**: The OID repository is constantly updated but does not necessarily store the latest (or most accurate) version of this formal description. For an implementation, it is recommended to search the web for a more recent description. If this is the case, please update the above description.