## OID: `1.3.6.1.4.1.534.6.6.7.6.1.1.7`

```asn1
{iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) 534 products(6) pduAgent(6) eatonEpdu(7) outlets(6) outletTable(1) outletEntry(1) outletPhaseID(7)}
```

### Description

```asn1
outletPhaseID OBJECT-TYPE
SYNTAX INTEGER {singlePhase(1), phase1toN(2), phase2toN(3), phase3toN(4), phase1to2(5), phase2to3(6), phase3to1(7), phase12N(8), phase23N(9), phase31N(10), phase123(11), phase123N(12)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Value indicates which phases are connected to each outlet in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2,
phase 2 to phase 3, phase 3 to phase 1, split-phase with phases 1 and 2, split phase
with phases 2 and 3, split phase with phases 3 and 1, three-phase delta, and three-phase wye."
```

**Classification:** MIB object for network management

### Child OIDs

No child OID

### Terms of Use

[Terms of use](https://oid-base.com/disclaimer.htm.md)

**Note to implementers:**: The OID repository is constantly updated but does not necessarily store the latest (or most accurate) version of this formal description. For an implementation, it is recommended to search the web for a more recent description. If this is the case, please update the above description.