oid: "1.3.6.1.4.1.52.4.1.5.4.1.6.1.1.2"
asn1-notation: "{iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) 52 mibs(4) ctron(1) ctSystem(5) ctUPowerSupply(4) ctUPS(1) upsStatus(6) upsStatusTable(1) upsStatusEntry(1) upsStatusFault(2)}"
description: "upsStatusFault OBJECT-TYPE"
last-modified: "2017-12-05"
tags: [oid-repository]
---

## OID: `1.3.6.1.4.1.52.4.1.5.4.1.6.1.1.2`

```asn1
{iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) 52 mibs(4) ctron(1) ctSystem(5) ctUPowerSupply(4) ctUPS(1) upsStatus(6) upsStatusTable(1) upsStatusEntry(1) upsStatusFault(2)}
```

### Description

```asn1
upsStatusFault OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"This object contains 8 bits of information about the current
fault conditions of the UPS. The bits are encoded as
follows:
BIT 7: 1=UPS fault - internal temperature has exceeded
nominal limits
BIT 6: 1=UPS fault - bypass relay (where applicable) malfunction
BIT 5: 1=UPS fault - battery charger failure
BIT 4: 1=UPS in shut down mode via `S' command
BIT 3: 1=UPS in `sleep' mode via `@ddd' command
BIT 2: 1=UPS fault - main relay malfunction
BIT 1: 1=UPS unable to transfer to on-battery operation
due to overload
BIT 0: 1=UPS's output unpowered due to low battery shut down
Note that bit 0 is the low-order bit."