oid: "1.3.6.1.4.1.38446.4.1.6.1"
short-description: "trapCritical NOTIFICATION-TYPE"
last-modified: "2022-07-26"
parent-oid: "1.3.6.1.4.1.38446.4.1.6"
---

## OID: `1.3.6.1.4.1.38446.4.1.6.1`

```asn1
{iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) 38446 es(4) pdu(1) pduTraps(6) trapCritical(1)}
```

### Description

```asn1
trapCritical NOTIFICATION-TYPE
OBJECTS {trapCode, trapDescription, trapDeviceDescr, trapDeviceMgmtIP}
STATUS current
DESCRIPTION
"A critical alarm has occurred. Action: Check the Trap Details for more information."
\-- #TYPE "Critical Alarm"
\-- #SEVERITY CRITICAL
\-- #CATEGORY "PowerDevice"
\-- #SIMPLE_SEVERITY CRITICAL
\-- #HWSTATUS_CATEGORY POWER
\-- #SUMMARY " %s from %s %s"
\-- #ARGUMENTS {2, 3, 0}
\-- PDU Critical Alarm trap text: Description:
\-- Voltage High Critical The PDU has detected an input line voltage that is more than 20% ABOVE the expected voltage
\-- Voltage Low Critical The PDU has detected a very low input line voltage more than 20% BELOW the expected voltage, or the breaker may have tripped.
\-- Load Critical The rated capacity of the breaker has been exceeded. There is a high risk of tripping the breaker
\-- Current Critical Current has exceeded the breaker rating level. The addition of any new load could overload or trip the breaker
\-- Total Power Critical The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection
\-- Total Heat Critical The heat created by the load attached to this PDU has exceeded the set threshold
\-- Total Load Critical The rated capacity of the PDU has been exceeded. There is a risk of tripping the branch circuit protection
\-- iPDU Critical Alarm trap text: Description:
\-- Voltage High The voltage for the iPDU is above the warning or critical limit
\-- Voltage Low The voltage for the iPDU is below the warning or critical limit
\-- Total PDU Load The total load of the iPDU is above the warning or critical limit
\-- Phase Load The phase load is above the warning or critical limit
\-- Load Segment Current The current for the circuit breaker is above the warning or critical limit
\-- Managed Ext. Bar Communication An Intelligent Extension Bar can no longer communicate with the iPDU
\-- Display Communication The Display Module can no longer communicate with the iPDU
\-- Redundant Communication The iPDU cannot communicate with the redundant PDU or there is a redundancy configuration error
\-- Remote PDU IP Mismatch The redundant PDU is already configured for redundancy with another PDU
\-- Remote Outlet Control Disabled The redundant PDU outlet control settings are disabled and will therefore not allow redundant management control of its outlets
\-- PDU Communication The Primary iPDU cannot communicate with the Secondary ipdu
```

**Classification:** MIB object for network management

### Child OIDs

No child OID

### Terms of Use

[Terms of use](https://oid-base.com/disclaimer.htm.md)

**Note to implementers:**: The OID repository is constantly updated but does not necessarily store the latest (or most accurate) version of this formal description. For an implementation, it is recommended to search the web for a more recent description. If this is the case, please update the above description.