oid: "1.3.6.1.4.1.38446.1.4.2.1.4"
short-description: "pduCircuitBreakerConfigOverloadRestriction OBJECT-TYPE"
last-modified: "2022-07-26"
parent-oid: "1.3.6.1.4.1.38446.1.4.2.1"
---

## OID: `1.3.6.1.4.1.38446.1.4.2.1.4`

```asn1
{iso(1) identified-organization(3) dod(6) internet(1) private(4) enterprise(1) 38446 pdu(1) pduCircuitBreaker(4) pduCircuitBreakerConfigTable(2) pduCircuitBreakerConfigEntry(1) pduCircuitBreakerConfigOverloadRestriction(4)}
```

### Description

```asn1
pduCircuitBreakerConfigOverloadRestriction OBJECT-TYPE
SYNTAX INTEGER {alwaysAllowTurnOn(1), restrictOnUpperWarning(2), restrictOnUpperCritical(3), notSupported(4)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This OID controls the behavior of a Switched PDU Circuit
Breaker when an overload condition is possible and additional
outlets are requested to be turned on. Setting this OID to
alwaysAllowTurnON (1) will always allow the outlets on the
corresponding Circuit Breaker to turn on. Setting this OID
to restrictOnUpperWarning (2) will not allow outlets on the
corresponding Circuit Breaker to turn on if the
pduCircuitBreakerConfigUpperWarningThreshold OID is exceeded.
Setting this OID to restrictOnUpperCritical (3) will not
allow outlets on the corresponding Circuit Breaker to turn
on if the pduCircuitBreakerConfigUpperCriticalThreshold OID
is exceeded. Models that do not support this feature will
respond to this OID with a value of notSupported (4).
Attempts to set this OID in these models will fail."
```

**Classification:** MIB object for network management

### Child OIDs

No child OID

### Terms of Use

[Terms of use](https://oid-base.com/disclaimer.htm.md)

**Note to implementers:**: The OID repository is constantly updated but does not necessarily store the latest (or most accurate) version of this formal description. For an implementation, it is recommended to search the web for a more recent description. If this is the case, please update the above description.