oid: "1.3.6.1.2.1.33.1.2.1"
short-description: "upsBatteryStatus OBJECT-TYPE"
last-modified: "2020-03-04"
parent-oid: "1.3.6.1.2.1.33.1.2"
---

## OID: `1.3.6.1.2.1.33.1.2.1`

```asn1
{iso(1) identified-organization(3) dod(6) internet(1) mgmt(2) mib-2(1) upsMIB(33) upsObjects(1) upsBattery(2) upsBatteryStatus(1)}
```

### Description

```asn1
upsBatteryStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
batteryNormal(2),
batteryLow(3),
batteryDepleted(4)
}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The indication of the capacity remaining in the UPS
system's batteries. A value of batteryNormal
indicates that the remaining run-time is greater than
upsConfigLowBattTime. A value of batteryLow indicates
that the remaining battery run-time is less than or
equal to upsConfigLowBattTime. A value of
batteryDepleted indicates that the UPS will be unable
to sustain the present load when and if the utility
power is lost (including the possibility that the
utility power is currently absent and the UPS is
unable to sustain the output)."
```

**Classification:** MIB object for network management

### Supplementary information

Automatically extracted from IETF [RFC 1628](https://www.rfc-editor.org/rfc/rfc1628.html).

### Child OIDs

No child OID

### Terms of Use

[Terms of use](https://oid-base.com/disclaimer.htm.md)

**Note to implementers:**: The OID repository is constantly updated but does not necessarily store the latest (or most accurate) version of this formal description. For an implementation, it is recommended to search the web for a more recent description. If this is the case, please update the above description.